LED Backup Light, LED Emergency Recessed Downlight
Basic Info
Model NO. | LEK02-3NC |
Battery Type | Ni-Cd Battery |
Emitting Color | Cool White |
Material | Aluminum |
Certification | CE, RoHS, CB |
Warranty | 2 Years |
IP | 20 |
Transport Package | Color Box |
Specification | 40mm Cutout hole |
Trademark | flolite |
Origin | China |
HS Code | 8504401400 |
Production Capacity | 3000PCS/Day |
Product Description
CB Approved 3W LED Emergency light with Ni-Cd batteries 3Hours BackupRelevant Standard
EN 60598-1 | EN 61000-3-2 | IEC 60598-1 | IEC61000-3-2 |
EN 60598-2-22 | EN 61000-3-3 | IEC 60598-2-22 | IEC 61000-3-3 |
EN 61347-1 | EN 62471 | IEC 61347-1 | IEC 62471 |
EN 61347-2-13 | EN 62493 | IEC 61347-2-13 | IEC 62493 |
EN 61347-2-7 | EN 55015 | IEC 61347-2-7 | IEC 55015 |
EN 62778 | EN62031 | IEC 62778 | IEC62031 |
Product Parameter
Model No.: | LEK02-3NC | Battery: | Ni-Cd, 3.6V 2000mAh |
LED Chips: | CREE XT-E | Luminous Flux: | 150lm |
Power Consumption: | 3W | Input Voltage: | AC220-240V~50/60Hz |
Charge time: | 24Hours | Emergency duration: | 3Hours |
ta: | 0~35ºC | Max. Case Temp.: | 70ºC |
Protection Class: | II | IP Rating: | IP20 |
Operation: | Non-maintained | Function: | AUTO test |
Dimension
Installation Diagram
Wire preparation:
0.5~1.5mm²
AUTO Test
∷ Commissioning test-
Connection of the mains supply will initiate commissioning where the battery will remain on charge for an uninterrupted 24 hours; An interruption of the mains supply will reset the counter to zero.
After 24hours, the luminaire will be put into a duration test for the rated period, immediately followed by another 24hr charge period.
∷ Function test-
A 5 second functional test is carried out at 1 week interval.
∷ Duration test-
A full rated duration test is carried out at 13 weeks intervals.
System status is indicated by a bi-color LED.
LED indication | Status | Commentary |
Permanent green | Everything works correctly | |
One flashed 4 seconds pause | Battery failure | Battery is not connected |
Two flashed 4 seconds pause | Battery failure | Battery short or low battery Voltage |
Three flashed 4 seconds pause | Load failure | LED failure |
Green and Red off | DC mode | Battery operation (Emergency mode) |
Special Notes
∷ This product should be installed by a registered electrician in accordance with local standards and electrical regulations;
∷ Take care to ensure the mains supply is isolated before installation;
∷ The light source of this luminaire is not replaceable; when the light source reaches its end of life, the whole luminaire shall be replaced;
∷ The whole luminaire should be replaced when they no longer meet their rated duration of operation after the corresponding recharge period.